Skip to main content
Commercial kitchen extraction cleaning across London · Photos and TR19 records · 07843 141416
Duct Clean London

TR19 Grease Thickness Limits: 200, 500 and 50 Microns Explained

Quick answer: TR19 Grease, the BESA specification for kitchen extract systems, uses three grease thickness figures. A mean of 200 µm across the system means the whole extract needs cleaning. Any single reading over 500 µm needs that area cleaned straight away. After a clean, published summaries of the specification give a post-clean target of 50 µm or less. Readings are taken with a wet film thickness test at set points from the canopy to the discharge.

This guide from Duct Clean London explains what each limit means, how the readings are taken, and what to look for in your report.

The three TR19 grease limits at a glance

Measurement Limit What it means
Mean deposit across the system 200 µm The system needs a full clean. The cleaning interval is probably too long.
Any single reading Over 500 µm Clean that section immediately, whatever the schedule says.
Post-clean verification 50 µm or less The target the cleaned surfaces should be brought down to.

1 micron (µm) is one thousandth of a millimetre. 200 µm is about the thickness of two sheets of printer paper. That may sound small, but a 200 µm film spread along a whole duct route is a continuous fire load running through your building.

Why TR19 measures grease instead of looking at it

A canopy can look clean while the duct behind it is coated. Grease that gets past the filters cools and settles inside the plenum, the first few metres of duct, bends, risers and the fan. TR19 Grease replaces “looks fine” with a number, so the operator, insurer and fire risk assessor can all see the same evidence.

How the readings are taken

  • Wet film thickness test (WFTT): a notched gauge pressed into soft grease. The deepest tooth that picks up grease gives the reading.
  • Deposit thickness test (DTT): used for harder, baked-on or carbonised deposits that a wet film gauge cannot read.
  • Locations: readings are taken at representative points along the route, typically behind the canopy filters, in the duct close to the canopy and further along, before the fan, in the fan housing and in the discharge.

Readings should be taken from the same positions before and after cleaning, so you can compare like with like.

What happens if a reading is over the limit?

  1. Mean over 200 µm: book a full system clean and shorten the interval. If you are on a 6-month cycle and keep exceeding 200 µm, move to 3 months.
  2. Single reading over 500 µm: that section is a priority. It is often the first bend after the canopy, a horizontal run or the fan.
  3. Section not accessible: it cannot be measured or certified. The report should say so and recommend a fix, such as fitting an access panel.

How the limits link to cleaning frequency

TR19 Grease sets minimum cleaning intervals by daily cooking hours. The grease readings tell you whether that interval is working.

Kitchen use Cooking hours a day Clean at least every
Heavy 12–16 hours 3 months
Moderate 6–12 hours 6 months
Light 2–6 hours 12 months

Chargrills, woks and fryers load a duct faster than the hours alone suggest. Read our full guide on how often kitchen extraction should be cleaned.

What your TR19 report should show

  • Pre-clean and post-clean readings in microns, with the location of each one
  • Before and after photographs taken from the same positions
  • A sketch or schematic of the duct route and access points used
  • Any sections not reached, with the reason and a recommended fix
  • The recommended date for the next clean

A report with no numbers, or one that only covers the canopy, will not tell an insurer much. See what is included in our TR19 cleaning in London service, and our practical guide to TR19.

Sources

Frequently asked questions

What is the TR19 grease limit?

TR19 Grease uses a mean of 200 microns across the system as the trigger for a full clean. Any single reading over 500 microns needs immediate local cleaning.

What grease thickness should be left after a TR19 clean?

Published summaries of TR19 Grease give a post-clean target of 50 microns or less on cleaned surfaces, measured at the same points as the pre-clean readings.

How is grease thickness measured in a kitchen duct?

With a wet film thickness test for soft grease, or a deposit thickness test for hard, baked-on deposits, taken at set points from the canopy to the discharge.

Is 200 microns a legal limit?

No. TR19 Grease is industry guidance from BESA, but insurers and fire risk assessors use it to judge whether the fire risk from grease is being managed under the Regulatory Reform (Fire Safety) Order 2005.

Does Duct Clean London take grease readings?

Yes. We take readings before and after cleaning at the canopy, duct runs and fan, and record them with photographs in your report.

Book a measured clean in London

Duct Clean London cleans canopies, filters, ductwork and extract fans across North West, West and Central London (Zones 1–4), with grease readings and photographs in every report. Call 07843 141416 or send a booking enquiry with your postcode and a few photos of your system.

Related: Duct Clean London home · All services · TR19 cleaning London · All guides

    Ready to plan your next clean?

    Tell us about your site, the system and your preferred timing. We will contact you to agree the right scope and next steps.
    Duct Clean London

    Duct Clean London

    Commercial kitchen extraction and ventilation cleaning.
    71-75 Shelton Street, London WC2H 9JQ
    North West, West and Central London · Zones 1–4 enquiries welcome.
    © 2026 Duct Clean London Ltd





    Your kitchen extraction clean, from survey to report


    Duct Clean London plans the accessible canopy, filters, ductwork, fan and discharge route as one connected system.



    01

    Review the system

    We check photographs, opening hours, cooking type, previous reports and the extraction route.


    02

    Agree access

    We identify access panels, high-level areas, risers, roof restrictions and safe working requirements.


    03

    Clean the scope

    Our engineers degrease the agreed accessible canopy, filters, ducts and fan components.


    04

    Record the work

    You receive post-clean photographs, a cleaning record and clear notes about limitations or follow-up.



    Canopy & filtersDuctworkExtraction fansTR19-aligned reportingLondon Zones 1–4

    Request a free quote





    See our latest work on TikTok


    Follow @ductcleanlondon for recent kitchen extraction and duct-cleaning videos.


    @ductcleanlondon on TikTok

    Open our TikTok profile






    Our London service area


    Explore the live map below. We mainly cover North West, West and Central London, including many locations within travel Zones 1–4. Send your full postcode so we can confirm access and availability.


    Main service area

    View Duct Clean London on Google Maps





    Rated 5.0 by our customers


    ★★★★★

    5.0 · 12 Google reviews

    See our Google Business Profile for customer feedback, photos, opening information and contact details.


    View Duct Clean London on Google








    5.0 Google rating12 customer reviews